3M Completes Its Longest Known Running ACCR Field Test

High-Capacity Aluminum Conductor Withstands 13-years in Minnesota Climate

3M recently completed its longest known field test of a composite conductor in the United States, a 13-year field test of the 3M Aluminum Conductor Composite Reinforced (ACCR). Installed in 2001 on a 115 kV transmission line at Xcel Energy’s Riverside Plant in Minneapolis, the test demonstrated the strength and resiliency of 3M’s ACCR composite conductor in demanding environmental conditions.

This field trial installation was the first known installation of a composite conductor of any kind in the U.S. transmission grid. The conductor was installed in 2001 and operated continuously until it was taken down for testing in December of 2014. Since the Xcel Energy installation, 3M conducted additional field tests at other utilities and at the U.S. Department of Energy outdoor testing facility at Oak Ridge National Lab. However, the Xcel Energy Riverside Plant test remains the longest running of all 3M ACCR field tests.

The wide-ranging temperatures and changing weather conditions in Minnesota, from high heat and humidity during the summer months to extreme cold and heavy ice loads in the winter, provided an ideal test environment. The 3M ACCR 477 kcmil Hawk conductor was installed on a span of a 115 kV transmission line at Xcel Energy’s Riverside Plant, located on the banks of the Mississippi River in Minneapolis. The ACCR composite conductor, which ran from the 511 MW Riverside Plant to the transmission substation, operated in ambient temperatures ranging from -40 F in the winter to more than 100 F in the summer.

The ACCR composite conductor met or exceeded expectations in all levels of line performance. Core samples of the ACCR conductor showed no sign of tensile strength loss, with results ranging from 108 percent to 110 percent of rated breaking strength. While the conductor was still in the air, sag-tension was measured and matched optimum performance expectations of 2990 lbs. at 20 F.

“The Xcel Energy installation was an ideal environment in which to test the strength and durability of the ACCR composite conductor,” commented Herve Deve, technical manager, 3M Electrical Markets Division. “The testing demonstrates the long term durability of the ACCR and the performance attributes of the line in extreme environmental conditions over time.”

“Our customers need to know that the 3M ACCR composite conductor can stand the tests of weather, load and time. Moreover, they need to know that performance standards can be maintained over time, regardless of most environments, or the demands,” noted Fred Schiller, business director, 3M Electrical Markets Division. “This test, together with similar tests around the globe, illustrate the resiliency of the high-capacity, low-sag, lightweight ACCR overhead conductor.”

3M ACCR was introduced commercially in 2005 and is now installed on six continents.

Because its light weight and low sag properties often enable line upgrades without the need to construct larger towers or expand rights of way, the conductor has found widespread use wherever tower replacement is difficult or uneconomical, including crowded urban settings and environmentally sensitive locations, such as river crossings and estuaries.

3M ACCR was developed with the support of the U.S. Department of Energy, which tested the conductor at its Oak Ridge National Laboratory (ORNL) in Tennessee, and with early contributions by the Defense Advanced Research Projects Agency. The ORNL tests demonstrated that the conductor retains its integrity after exposure to temperatures even higher than the rated continuous operating temperature of 210 C and the emergency operating temperature of 240 C. It has the durability and longevity of traditional steel core conductors, even when operated continuously at high temperatures.

The conductor’s strength and durability result from its core, composed of aluminum oxide (alumina) fibers embedded in high-purity aluminum, utilizing a highly specialized and proprietary process. The constituent materials can withstand high temperatures without appreciable loss in strength. Also, since 3M's ACCR is based on aluminum, it has the corrosion resistance typically associated with all-aluminum conductors.

3M holds several patents on its ACCR technology, which has been recognized by R&D Magazine with an R&D 100 Award as one of the most technologically significant products introduced into the marketplace, and by the Minnesota High Tech Association with a Tekne Award for innovative development.

Since the invention of vinyl electrical tape in 1946, the 3M Electrical Markets Division has designed and manufactured reliable products for some of the world’s leading industries, including energy, commercial and industrial electrical construction, oil and gas, mining, water, transportation and manufacturing. Today, the division deploys technology to create new solutions to help meet energy and infrastructure challenges.

More information about the 3M high capacity conductor is available at www.3M.com/accr. Video of the field installation also available.

About 3M
At 3M, we apply science in collaborative ways to improve lives daily. With $30 billion in sales, our 90,000 employees connect with customers all around the world. Learn more about 3M’s creative solutions to the world’s problems at www.3M.com or on Twitter @3M or @3MNewsroom.

3M is a trademark of 3M Company.
All other trademarks listed herein are owned by their respective companies.

3M Public RelationsJane Kovacs, 512-984-6747jkovacs@mmm.com

Multimedia Files:

3M™ Aluminum Conductor Composite Reinforced (ACCR) is installed in the first field test of a composite conductor in the United States on March 27, 2001, at Xcel Energy’s Riverside Plant in Minneapolis. Photo courtesy of 3M
 

Other Topics

Contact Media Relations

Contact Media Email
 

These contacts are intended only for the media. If you are not a member of the media, please call 1-888-3M HELPS (1-888-364-3577).
 

We will get back to you within one business day.

Email Alerts

Subscribe to receive automatic updates via email for 3M news & stories.

Subscribe